Thank you for taking interest in Military Specifications part number MIL-PRF-55629/4, which is listed with the NSN 5925-01-204-0456 and a product description of “Circuitbreaker.” In order to receive procurement options on this particular listing, we ask that you fill out and submit the form provided below with as much information as you can concerning your needs. By supplying our staff with key details on your desired quantity, pricing target, and expedited fulfillment timeframe, we can respond with a quote that has been specifically tailored to your unique specifications. We also ask that you make us aware of any restrictions that you may have as soon as possible, such as if you have a time constraint or are seeking unlisted items.
Note : We Will Not Share Your Information To Any Third Parties.
Alongside part number MIL-PRF-55629/4, you are encouraged to continue exploring our collection curated catalogs to find additional items that can accompany this Circuitbreaker part with the NSN 5925-01-204-0456. For example, you can browse other Military Specifications components that were produced under CAGE Code 81349 or listings that belong to FSC 5925 Circuit Breakers with ease on our website, with search tools provided for quick location. Furthermore, our staff is just a call or email away from assisting you with any inquiries or requests, so be sure to get started on the quotation process for part number MIL-PRF-55629/4 and other desired offerings on Aerospace Spare.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-01-204-0456 Item PartTypeName: CIRCUIT BREAKER | 5925 | 012040456 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | U | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
M55629/4-032 | 5 | 2 | 2 |
MRC | Criteria | Characteristic |
---|---|---|
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF |
CWJK | CASE MATERIAL | PLASTIC |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
TEST | TEST DATA DOCUMENT | 81349-MIL-C-55629 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS,BROCHURES,ETC.,THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS,INDUSTRY DIRECTORIES,AND SIMILAR TRADE PUBLICATIONS,REFLECTI |
THSD | THREAD SERIES DESIGNATOR | UNC |
TTQY | TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
ZZZK | SPECIFICATION/STANDARD DATA | 81349-MIL-C-55629/4 GOVERNMENT SPECIFICATION |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 1.969 INCHES MINIMUM AND 2.031 INCHES MAXIMUM |
ADAT | BODY WIDTH | 1.469 INCHES MINIMUM AND 1.531 INCHES MAXIMUM |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.529 INCHES MINIMUM AND 1.591 INCHES MAXIMUM |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.719 INCHES MINIMUM AND 0.781 INCHES MAXIMUM |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.629 INCHES MINIMUM AND 1.691 INCHES MAXIMUM |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.719 INCHES MINIMUM AND 0.781 INCHES MAXIMUM |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AGAV | END ITEM IDENTIFICATION | COMMON DIGITIZER 2C (CD2C) |
AJEC | BOSS HEIGHT | 0.099 INCHES MINIMUM AND 0.161 INCHES MAXIMUM |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.000 INCHES MINIMUM AND 2.031 INCHES MAXIMUM |
AKPX | POLE QUANTITY | 2 |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 3.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.130 MINIMUM AT 200 PCT AND 1.600 MAXIMUM AT 200 PCT ALL LOCATIONS |